Industrial Heaters Specifications


Industrial Heater


Rating
(Input: Natural and L.P. Gas)

 

Model
Input
Min Length
Max Length
SR-40 40,000BTU/hr
10'
20'
SR-50 50,000BTU/hr
20'
20'
SR-60 60,000BTU/hr
20'
40'
SR-75 75,000BTU/hr
20'
40'
SR-80 80,000BTU/hr
20'
40'
SR-100 100,000BTU/hr
30'
50'
SR-125 125,000BTU/hr
40'
50'
SR-150 150,000BTU/hr
40'
60'
SR-175 175,000BTU/hr
50'
70'
SR-200 200,000BTU/hr
60'
80'

Gas Pressure at Manifold:
Natural Gas 3.5" W.C.
L.P. Gas 10.5" W.C.
Gas Connection Size 0.5" N.P.T.

Gas Inlet Pressure:
Gas Minimum
Maximum
Natural 4.5" W.C.
14.0" W.C.
L.P. 11.5" W.C.
14.0" W.C.
Flue Connection  
4"
Combustion Air Intake
(SR-40 to SR-100) 4"
 
(SR-125 to SR-200) 6"

 

Electrical Rating:
DSI Ignition
120v, 60 Hz, 1 Amp
1.0 Amp SR-40 to SR-125
2.25 Amp SR-150 to SR-200

 

Standard Equipment:
Burner control housing is preassembled and pre-wired, unit comes complete with industry standard gas, electrical and venting connections, balanced air rotor, thermal overload protected motor, visual burner inspection sightglass, combustion and air proving safety switch, 3-try spark ignition control, low voltage thermostat connection, 4" aluminized combustion tube, aluminum standard reflector, 4" mild steel radiant heat exchanger, tube couplers, joint/hanger pieces, heat economizer baffle.

 

Optional Equipment:

Side Reflectors Elbow kit
Aluminized Steel Tube Thermostat
Side Wall Vent Kit U-Bend kit
Stainless Steel